VSG-12 Indoor High Voltage Vacuum Circuit Breaker with Nylon Poles (12kV VCB)

VSG-12 series indoor high voltage vacuum circuit breaker is an advanced switchgear designed for 12kV triphase AC 50Hz power systems. Featuring a specialized nylon pole (nylon tube) construction, this 12kV VCB offers superior insulation reliability and mechanical stability in demanding environments.

产品类别

VSG-12 Indoor High Voltage Vacuum Circuit Breaker with Nylon Poles

Product Overview

The VSG-12 series is a high-performance indoor vacuum circuit breaker (VCB) designed for three-phase AC 50Hz power systems with a rated voltage of 12kV. Featuring an advanced nylon pole (nylon tube) construction, this breaker ensures superior insulation reliability and mechanical stability.

It is a premier choice for the protection and control of electrical equipment in power plants, substations, and industrial and mining enterprises. The VSG-12 is highly compatible with various fixed-type medium voltage cabinets, including GG-1A(Z) and XGN2-12(Z).

Key Features

  • Enhanced Insulation: Utilizes specialized nylon poles to provide excellent dielectric strength and stable operation.

  • Standard Compliance: Fully accords with the GB 1984 standard for High Voltage AC Vacuum Circuit Breakers.

  • Versatile Operation: Can be equipped with CT17 or CT19 model spring energy store operating devices, or CD17/CD10A model DC magnetic operating devices.

  • Integrated Design: The frame structure houses the vacuum interrupters and operating mechanism, ensuring a compact and robust build for long-term service.

Technical Specifications & Application Environment

To ensure safe and reliable operation, the VSG-12 must be used within the following parameters:

Parameter Requirement
Ambient Temperature -25°C to +40°C
Altitude ≤ 1000 meters
Relative Humidity Daily average ≤ 95%; Monthly average ≤ 90%
Saturated Vapor Pressure Daily average ≤ 2.2kPa; Monthly average ≤ 1.8kPa
Earthquake Intensity Not exceeding 8 degrees

Installation Requirements

The installation site must be free from the following:

  • Fire or explosion hazards.

  • Serious filth or conductive dust (heavy pollution).

  • Chemical erosion or corrosive gases.

  • Violent or severe mechanical vibration.

Send Us Your Inquiry