VSG-40.5 Indoor High Voltage Vacuum Circuit Breaker with Embedded Poles – Dedicated for KYN61 Switchgear

The VSG-40.5 series is a high-performance indoor vacuum circuit breaker featuring advanced embedded poles technology. Designed specifically for KYN61-40.5(Z) switchgear systems, it operates at a rated voltage of 40.5kV with a three-phase AC 50Hz frequency. This robust VCB serves as an ideal control and protection unit for power plants, substations, and industrial enterprises, offering reliable performance for locations requiring frequent operations. With its flexible installation, it can be used as either a fixed type or a withdrawable type installed on a trolley.

产品类别

Product Overview

The VSG-40.5 Series Indoor High Voltage Vacuum Circuit Breaker is an advanced power distribution component designed for three-phase AC 50Hz systems with a rated voltage of 40.5kV. Featuring state-of-the-art embedded pole technology, this VCB provides superior insulation and protection for electrical equipment in power plants, substations, and industrial mining enterprises. It is specifically engineered to be the premier choice for KYN61-40.5(Z) switchgear cabinets, supporting both fixed and withdrawable installation forms.

Key Features 

  • Embedded Pole Technology: Offers enhanced environmental resistance and high dielectric strength compared to traditional insulation.

  • KYN61 Compatibility: Perfectly matched for seamless integration with KYN61 series high-voltage switchgear.

  • High Reliability: Designed for frequent operations with a mechanical life of up to 10,000 cycles.

  • Maintenance-Free: Utilizing vacuum as the interrupting medium ensures long-term stability without the need for frequent internal maintenance.

Technical Specifications 

Main Technical Parameters 

Item Unit Data
Rated Voltage kV 40.5
Rated Frequency Hz 50/60
Rated Current A 630 / 1250 / 1600 / 2000 / 2500
1min Power Frequency Withstand Voltage kV 95
Lightning Impulse Withstand Voltage (Peak) kV 185
Rated Short-circuit Breaking Current kA 20 / 25 / 31.5
Rated Operating Sequence O-0.3s-CO-180s-CO
Mechanical Life times 10000

Mechanical Characteristic Parameters 

Item Unit Data
Contact Opening Distance mm 20±2
Contact Overtravel mm 6±1
Average Closing Speed m/s 0.6±0.2
Average Breaking Speed m/s 1.2±0.2
Contact Closing Bounce Time ms ≤3
Circuit Resistance per Phase μΩ ≤80

Ambient Application Conditions 

To ensure optimal performance and safety, the following conditions must be met:

  • Temperature: -40°C to +40°C (Daily average ≤ 35°C).

  • Humidity: Daily average relative humidity ≤ 95%; Monthly average ≤ 90%.

  • Altitude: Not exceeding 1000m.

  • Environment: The installation site must be free from fire, explosion risks, heavy pollution, chemical erosion, or violent vibration.

Send Us Your Inquiry

We are always ready to assist you! Contact our team for expert support and personalized solutions.

滚动至顶部