Earthing switches and disconnectors are often shown next to each other on a switchgear drawing, and both are operated during maintenance. They do different jobs, carry different ratings and are subject to different interlocks. Confusing them leads to two common mistakes: specifying a disconnector where a load-breaking device is needed, or ordering an earthing switch without checking its making capacity.
What each device does
A disconnector (also called an isolator) provides a visible isolation gap between a circuit and its source. It is not intended to interrupt load current or fault current; it is operated after the circuit breaker has opened. Its ratings therefore focus on insulation level, short-time withstand current and, where specified, peak withstand.
An earthing switch connects a circuit to earth so that work can proceed safely. It is closed after the circuit is isolated, and it must withstand the short-circuit current that could flow through the earthing path until protection clears. Some earthing switches are also rated for making onto a fault (making capacity), which matters when the switch may be closed onto a live or charged circuit.
Both follow IEC 62271-102 for alternating-current disconnectors and earthing switches. A load break switch is a different device: it can interrupt load current, and is covered by its own requirements.
Ratings to compare
- Rated voltage and insulation level: both devices must match the system voltage and the lightning impulse withstand level of the panel.
- Rated normal current: the continuous current the device carries, usually matched to the panel busbar.
- Rated short-time withstand current and duration: the fault current the device can carry for the specified time, typically 1 s or 3 s.
- Rated peak withstand current: the first-cycle peak associated with the short-time current.
- Making capacity (earthing switch): whether the switch can be closed onto a fault, and at what current.
- Operating mechanism: manual, motor or spring-assisted, with the position indication and interlocks required by the panel.
An earthing switch without a stated making capacity should not be used for closing onto a circuit that may be live or charged. Where the design requires it, that rating belongs in the specification and on the nameplate.
Interlocks and operating sequence
The normal sequence is: open the circuit breaker, open the disconnector to create the isolation gap, then close the earthing switch. The interlocks should make that sequence the only possible one: the disconnector cannot be operated with the breaker closed, and the earthing switch cannot be closed while the disconnector is closed. In a withdrawable panel, the position of the breaker truck adds another condition.
Key interlocks, mechanical interlocks and solenoid interlocks are all used. Whichever type is chosen, the logic must be documented in the panel drawing and tested during commissioning. An interlock that is wired but not tested is not an interlock.
Indoor and outdoor versions
Indoor disconnectors and earthing switches are usually part of a metal-clad or compartmented panel and are operated from the front. Outdoor versions need weatherproof enclosures, suitable clearances and, for motor-operated units, heaters and cable entries that suit the site. Coastal or humid sites require attention to creepage distance and to the materials used for insulation.
What to put in the enquiry
- System voltage, rated current and short-time withstand current with duration.
- Whether the earthing switch must have making capacity, and at what current.
- Indoor or outdoor installation, and the panel or enclosure type.
- Manual or motor operation, control voltage and required position contacts.
- Interlock scheme, key interlocks and any interface with the circuit breaker.
- Required standard, type test evidence and the drawing number for the interface.
With these items a supplier can confirm a model instead of matching by appearance. Browse the earthing switch and disconnector switch and isolator categories for typical configurations, or the load break switch category where load-current breaking is required.
FAQ
Can a disconnector be used to switch load current?
Not unless it is specifically designed and rated as a load break switch. A standard disconnector is an isolation device and must be operated after the circuit breaker has interrupted the current.
Does every earthing switch need a making capacity rating?
Only where it may be closed onto a live or charged circuit. If the interlock guarantees the circuit is dead before closing, the requirement can be different, but the specification should state which case applies.
Are the interlocks part of the switch or the panel?
Both are possible. Mechanical interlocks are often built into the switch or its operating mechanism, while key and solenoid interlocks are part of the panel scheme. The division of supply must be stated in the enquiry.
Send the panel drawing, ratings and interlock requirements through the contact form for a model check and quotation. For the breaker side of the same panel, see the vacuum circuit breaker spare parts guide.