Insulation is the part of a switchgear specification that is easiest to overlook and hardest to fix later. Clearances and creepage distances decide whether a panel can survive moisture, dust and voltage transients for twenty years — or whether it starts tracking after the first humid season. This checklist covers what a buyer can reasonably check before accepting a design.
Clearance versus creepage
Clearance is the shortest distance through air between two conductive parts. Creepage is the distance along the surface of an insulating material. They are limited by different mechanisms: clearance by the breakdown of air, creepage by surface contamination and tracking. A design can pass one and fail the other, especially in humid or polluted sites where the surface path matters more.
What drives the required distances
- System voltage and insulation level: the rated voltage and the lightning impulse withstand level set the baseline.
- Pollution degree: the site environment — clean indoor, industrial dust, coastal salt — changes the creepage requirement.
- Altitude: above the standard reference altitude, air insulation has to be corrected for the reduced density.
- Material: the comparative tracking index of the insulating material affects how much creepage is needed.
- Overvoltage category: the position of the panel in the system changes the transient level it must withstand.
These parameters come from the standard the switchgear is designed to, normally the IEC 62271 series for medium voltage. A supplier should be able to state the pollution degree and altitude the design assumes; if those do not match the site, the design needs review.
Where creepage gets lost
Creepage is usually consumed in the details: a busbar support that is slightly too close to a barrier, a cable termination that leaves a short surface path, an insulating sleeve that does not overlap far enough, or a phase barrier with a sharp edge that collects dust. These are rarely visible in a single-line diagram and only show up in the arrangement drawing or on site.
Ask for the insulation co-ordination drawing or the panel arrangement drawing, and check the path between phases and to earth at the tightest points: cable compartment, busbar joints, and the connection to the circuit breaker.
Materials and ageing
Epoxy resin, polyester and thermoplastic insulators age differently. Heat, ultraviolet light and pollution accelerate tracking. In outdoor or coastal installations, check that the material and the creepage are chosen for the environment rather than for a clean indoor laboratory. Surface contamination is the reason a design that passes a factory test can still fail in service.
Tests and evidence
Type tests on the switchgear design cover dielectric performance under defined conditions. Routine tests on the delivered panel check that the insulation is intact after assembly. Ask for the routine test report — power-frequency withstand on the main circuit and, where applicable, on the auxiliary circuit — and keep it with the panel documentation. For a retrofit, ask how the new components affect the original insulation co-ordination.
What to put in the enquiry
- System voltage and insulation level, including impulse withstand.
- Site conditions: indoor or outdoor, pollution level, altitude, humidity, coastal air.
- The standard and the overvoltage category the design must meet.
- Panel arrangement and the compartments where clearances are tight.
- The test reports expected at delivery.
FAQ
Is creepage the same as clearance?
No. Clearance is through air; creepage is along the surface of insulation. Both are specified, and both must be checked for the site conditions.
Does a higher voltage rating always fix a creepage problem?
No. A higher rating changes the required distances, but the actual arrangement must still provide them. Increasing the rating without changing the layout may not solve the issue.
Can insulation be improved after delivery?
Sometimes, with barriers, sleeves or a redesigned connection, but the clean solution is to fix it at the design stage. Retrofitting insulation into a tight compartment is limited by the space available.