FN7-12DR Indoor 12kV 3-Phase High Voltage AC Load Break Switch with Fuse and Earthing Switch

The FN7-12DR is a high-performance indoor AC high-voltage load break switch and fuse combination apparatus designed for 12kV, 50Hz three-phase power systems. It is an ideal solution for load current breaking and short-circuit protection in modern electricity networks. Engineered with high-quality raw materials and full oblique seams, it ensures superior durability and reliability. The unit features a thickened stainless steel shell and an integrated earthing switch capable of withstanding short-circuit currents, providing maximum safety for your electrical infrastructure.

Product categories

High-Voltage Indoor Load Break Switch Series (FN18 & FN7)

1. Product Overview

Our high-voltage indoor load break switch series includes the FN18 and FN7-12DR types, designed for reliable performance in medium-voltage distribution systems. These switches are essential building blocks for metal-enclosed and pad-mounted switchgear applications, particularly in city network construction, high-rise buildings, and transformer protection.

2. FN18 Series: Advanced Arc-Extinguishing Technology

The FN18 series is a three-pole, air-insulated switch that combines two proven technologies: compressed-air and gas-produced arc extinguishing.

  • Integrated Protection: When combined with a fuse, it combines the advantages of a load switch and a fuse to break load currents and short-circuit currents effectively.

  • Robust Construction: Built with a heavy-duty steel frame, stand-off insulators, and a puffer-type arc extinguishing system.

  • Standard Features: Includes blade-type interrupters with cast hinges and jaw connectors for high reliability and fast breaking speed.

  • Optional Accessories: Available with motor operators, auxiliary switches, shunt trip devices, and mechanical interlocking systems.

3. FN7-12DR Series: Compact and Efficient

The FN7-12DR type is an indoor AC off-voltage load break switch applicable to 50Hz, 12kV three-phase power systems.

  • Premium Materials: Adopts high-quality brand-new raw materials with full oblique seams.

  • Short-Circuit Resilience: Equipped with a grounding switch capable of withstanding short-circuit currents.

  • Enhanced Durability: Features a thickened stainless steel shell for superior protection.


4. Technical Specifications

Parameter FN18 (12kV) FN7-12DR
Rated Voltage 12kV 11kV – 12kV
Rated Current 400A / 630A / 1250A 400A / 630A
Short-Circuit Making Capacity 67kA Peak 31.5kA / 50kA
Dynamic Stable Current (Peak) 82kA Peak 31.5kA / 50kA
1min P.F. Withstand Voltage 42kV / 45kV 42kV / 48kV
Impulse Withstand Voltage 75kV / 85kV
Opening Time 40ms – 60ms

5. Usage Environment Requirements

To ensure optimal performance and longevity, the switches must be operated within the following conditions:

  • Ambient Temperature:

    • Maximum: +40°C.

    • 24-hour Average: +35°C.

    • Minimum: -15°C (according to “minus 5 indoor class”).

  • Humidity:

    • Daily Average Relative Humidity: ≤ 95%.

    • Monthly Average: ≤ 90%.

  • Atmospheric Pressure:

    • Daily Saturated Vapor Pressure: ≤ $2.2 \times 10^{-3}$ MPa.

    • Monthly Average: ≤ $1.8 \times 10^{-3}$ MPa.

  • Altitude: Maximum site altitude is 1000m above sea level.


Send Us Your Inquiry

We are always ready to assist you! Contact our team for expert support and personalized solutions.

Scroll to Top